This type of transformer is applicable to electric power systems of 5oHz and 11ok,used for current, electric energy measuring and replayingprotection.
This type of product is equipped with metal expander, ful-sealed structure, primary winding has U-shaped capacitor type insulation structure, hasadvantages of uniform electric field distribution, low dielectric dissipation rate, low partial discharge quantity, secondary winding usually has 3-6windings, class can be combined at random, we could produce urrent transtormers of measurement class accuracy of 0.2S for special purposesaccording to user's requirements.
This type of product is of outdoor type, ambient temperature -30°C ~+40°C.
LB6-110(LCWB6-110)is suitable for areas of altitude up to 1000m;LB6-110W2(LCWB6-110W2) is suitable for polluted areas of altitude up to 1000m;LB6-110GY(LCWB6-110GY) is suitable for plateau areas of altitude up to 3500m;LB6-110GYW2(LCWB6-110GYW2) is suitable for polluted plateau areas of altitude up to 3500m.
|
No. |
Item |
Unit |
Guaranteed value |
|||
|
1 |
Model |
|
LB-24 |
|||
|
2 |
Type |
|
Outdoor、single phase、oil immersed |
|||
|
3 |
Manufacturer |
|
Boerstn Electric Co.,Ltd |
|||
|
4 |
Origin |
|
China |
|||
|
5 |
Applicable standard |
|
IEC 61869-2 |
|||
|
6 |
Applicable altitude |
m |
≤1000 |
|||
|
7 |
Applicable ambient temperature |
℃ |
-40~+45 |
|||
|
8 |
Insulation level |
kV |
24/65/125 |
|||
|
9 |
Rated frequency |
Hz |
50 |
|||
|
10 |
System rated primary voltage |
kV |
20 |
|||
|
11 |
System max voltage |
kV |
24 |
|||
|
12 |
Rated primary current |
A |
800-1600 |
|||
|
Rated secondary current |
A |
1 |
||||
|
|
rated primary current ratio (A) |
Accuracy class |
rated secondary output (VA) |
|||
|
1S1,1S2,1S3 |
|
800-1600/1A |
5P20 |
30 |
||
|
|
|
|
|
|
||
|
13 |
power frequency withstand voltage of primary terminal |
kV |
65 |
|||
|
14 |
kV |
125 |
||||
|
15 |
kV |
/ |
||||
|
16 |
Partial discharge level |
PC |
1.2Um/√3 |
≤5 |
||
|
Um |
≤10 |
|||||
|
17 |
Dielectric loss |
|
10 |
680.21PF 0.18% |
||
|
18 |
Winding temperature rise |
K |
30 |
|||
|
19 |
Primary winding material |
|
||||
|
20 |
Secondary winding material |
|
Copper |
|||
|
21 |
Primary terminal pulling force |
N |
2000 |
|||
|
22 |
External insulation type |
|
High-strength porcelain/Brown |
|||
|
23 |
Pollution class |
|
E |
|||
|
24 |
Mininum creepage distance |
mm |
1150 |
|||
|
25 |
Minimum dry arc distance |
mm |
≥780 |
|||
|
26 |
Seismic resistance level |
|
≥0.3g |
|||
|
27 |
Radio inferference |
μV |
≤1000 |
|||
|
28 |
Insulation oil type/oil weight |
|
45# transformer oil/60kg |
|||
|
29 |
Transportation weight/N.W |
kg |
320/260 |
|||
|
30 |
Transportation dimension(L×W×H) |
mm |
820×820*1820 |
|||
.webp)
Note: 1. Measurement class and protection class full-tap products are available at request.
2. Digts in()in the column of ol weight and gross weligtht mean the oil welight and sross welght of LCwB6- 11oCWW2 products, digits in ()of ratedoutput mean the rated output when the rated secondary currentis 1A, digits in()of rated primary current mean the tapping current.
.webp)
1. Expander
2. Oil level window hole
3. Primary outgoing terminal
4. Connecting plate
5. Porcelain sleeve
6.Fuel tank
7. Secondary junction box
8. Nameplate
9.Grounding
10.Oildrainvalve
11. Secondary outlet hole O thirty