VS1(ZN63A)-12 Indoor High-Voltage Vacuum Circuit Breaker

VS1(ZN63A)-12 Indoor High-Voltage Vacuum Circuit Breaker

The VS1(ZN63A)-12 series indoor high-voltage vacuum circuit breaker (hereinafter referred to as the
“circuit breaker”) is suitable for three-phase AC power systems with a rated voltage of 12 kV, a frequency of
50 Hz, and a rated current of 630 A to 4000 A. It is widely used in power systems of industrial and mining
enterprises, power plants, substations, and similar installations for the control and protection of cables,
overhead lines, transformers, capacitor banks, motors, and other equipment. The circuit breaker is used in
conjunction with KYN28A-12 switchgear, and may also be installed in fixed switchgear such as XGN2. This
product complies with the requirements of IEC62271-100 High-voltage switchgear and controlgear - Part
100: Alternating-current circuit-breakers. Its performance reaches Class C2-E2-M2.
description1
Zipper closure 1/4 zip athletic pullovers for men. Stretchy, lightweight, fast-drying fabric for superior performance. REGULAR FIT - US standard sizes. An athletic fit that sits close to the body for a wide range of motion, designed for optimal performance and all day comfort. FEATURES - Quarter zip closure;Thumbholes on long sleeves to keep them in place during workout
product details

Key Features

a) All secondary control components are located directly at the front of the operating mechanism , making inspection and maintenance convenient;

b) Modular functional unit design with a rational structural layout , facilitating maintenance and servicing;

c) Fewer parts , simple structure , and easy operation;

d) The cam directly drives the main shaft to rotate , resulting in high transmission efficiency;

e) Based on a new design concept , no adjustment of latching engagement is required ;

f) Long-life design: mechanical life of 30 ,000 operations for low-current applications and 20 ,000 operations for high-current applications; maintenance-free for 10 ,000 operations , meeting the requirements of Class M2;

g) The mechanism may be fitted with either assembled insulating cylinders or solid-sealed pole main-circuit components;

h) When used at altitudes of 2000 m and below, the insulation requirements can be met without replacing any parts;

I) Direct interchangeability can be achieved with ZN63A (VS1)-12 and VD4-12 products .

 Service Conditions

a) Altitude: areas at 1000 m and below.

b) Ambient temperature: not higher than +40 ° C and not lower than -15 ° C (storage and transportation at - 30 ° C are permitted) .

c) Relative humidity: daily average not exceeding 95% , monthly average not exceeding 90%; saturated   vapor pressure , daily average not exceeding 2 .2 × 10- 3  MPa and monthly average not exceeding 1 .8 × 10- 3 MPa . Condensation may occur when the temperature drops sharply during periods of high humidity.

d) Seismic intensity: not exceeding magnitude 8.

e) The installation site shall be free from dripping water, steam , flammable gas , fire hazards , explosion hazards , chemical corrosion , and severe vibration .

 Technical Data

Main Technical Data of the VS1(ZN63A)- 12 Series Indoor Vacuum Circuit Breaker

No .

Parameter

Unit

Data

1

Rated voltage

Kv

12

2

Rated frequency

Hz

50

3

Rated

insulation

level

1 min power-frequency withstand voltage

Kv

42

Rated lightning impulse withstand voltage

Kv

75

4

Rated current

A

630

1250

1600

2000

2500

3150

4000

 

 

5

Rated short-circuit breaking current

Rated short-time

withstand current (r. m .s .)

 

 

KA

20

20

 

 

 

 

 

25

25

 

 

 

 

 

 

31.5

31.5

31.5

31.5

31.5

31.5

 

40

40

40

40

40

40

 

 

6

Rated short-circuit making current (peak)

Rated peak withstand current

 

 

KA

50

50

 

 

 

 

 

63

63

63

 

 

 

 

 

80

80

80

80

80

80

 

100

100

100

100

100

100

7

Number of operations at rated short-circuit breaking current

times

50 ,20*

8

Rated short-time withstand duration

s

4

9

Rated operating sequence

 

O-0 .3 s-CO- 180 s-CO*

10

Mechanical life

times

10000

11

Rated single capacitor bank breaking current

A

400/630

12

Rated back-to-back capacitor bank breaking current

A

400

Note:

1 . When the rated short-circuit breaking current is ≤ 31 .5 kA , the number of operations at rated short-circuit breaking current is 50.

When the rated short-circuit breaking current is >31 .5 kA , the number of operations at rated short-circuit breaking current is 20.

2 . When the rated short-circuit breaking current is 40 kA , the rated operating sequence is: O-180 s-CO-180 s-CO.

3. Items 11 and 12 are rated parameters to be provided when required.

Mechanical Characteristics of the Circuit Breaker After Assembly and Adjustment

No .

Parameter

Unit

Data

1

Contact opening distance

mm

9±1

2

Contact travel

mm

3.5±0 .5

3

Three-phase opening/closing simultaneity

ms

≤2

4

Closing contact bounce time

ms

≤2

5

Centre-to-centre phase spacing

mm

210±1 .5(275±1 .5)

6

Rated short-circuit breaking current

kA

20

25

31.5

40

50

7

Closing contact pressure

N

2000±200

2400±200

3100±200

4500±200

6000±200

8

Average opening speed

m/s

1.2±0 .2

9

Average closing speed

m/s

0.7±0 .2

10

Opening time

ms

≤50

11

Closing time

ms

≤70

12

Main circuit resistance per phase

µΩ

≤50 (630 A- 1250 A) ≤45 (1600 A) ,≤35 (2000 A) ≤25 (2500 A and above)

13

Permissible wear thickness of moving and fixed contacts

mm

≤3

Technical Data of Closing Coil and Opening Coil

Closing/Opening Coil

Interlocking Coil

Anti-pumping Relay

Rated operating voltage (V)

DC220

DC110

DC220

DC110

DC220

DC110

Coil power (W)

198

198

4.4

2.7

1.0

Rated current (A)

0.9

1.8

20mA

25mA

9. 1mA

Operating voltage range

85% to 110% of rated voltage

65% to 110% of rated voltage

Technical Data of Charging Motor

Rated voltage (V)

Rated power (W)

Normal operating voltage range (V)

Charging time at rated voltage (s)

DC220    DC110

90

(0 .8-1. 1) times rated voltage

≤15