ZN85-40.5KV Indoor Vacuum Circuit Breaker (VCB)

ZN85-40.5KV Indoor Vacuum Circuit Breaker (VCB)

ZN85-40.5/T □ -□( 3AV3)-series handcart type indoor vacuum circuit breaker for three-phase AC 50Hz/60Hz,40.5KV power system, it's comply with standard of IEC62271-100, it's for industrial and mining enterprises, power plants and substations as the division and load current, overload current fault current purposes, and occasions for frequent operation.
description1
Zipper closure 1/4 zip athletic pullovers for men. Stretchy, lightweight, fast-drying fabric for superior performance. REGULAR FIT - US standard sizes. An athletic fit that sits close to the body for a wide range of motion, designed for optimal performance and all day comfort. FEATURES - Quarter zip closure;Thumbholes on long sleeves to keep them in place during workout
PRODUCT DETAILS

The use of environmental conditions

  • Altitude: ≤2000m;
    Air temperature: -55℃ ~ +45℃;
    Relative humidity: daily average is not more than 95%, saturated vapor pressure daily average is not more than 1.8kPa.
    Earthquake intensity: not more than eight. Installation places: No fire, explosion hazard, serious filthy places.
    In the second system, the amplitude of induced electromagnetic interference does not exceed 1.6kv
    Power condition: DC 110V, 220V; AC 110V, 220V
    If the client have other special request, please rise up when ordering.

Product model and meaning:

  • ZN85-40.5/T
    Vacuum circuit breaker
    Rated short-circuit breaking current(KA)
    Indoor type
    Rated current (A)
    Series number
    Actuator type
    Rated voltage

General structure drawing and installation size:

    Mainly technical parameters

      No

      Item

      unit

      parameter

      1

      Rated voltage

      KV

      40.5

      2

      1min power frequency withstand
      voltage(RMS)

      KV

      95

      3

      Lighting impulse withstand
      voltage(peak)

      KV

      185

      4

      Rated frequency

      Hz

      50/60

      5

      Rated current

      A

      1250, 1600, 2000,2500,3150

      6

      Rated short time withstand
      current

      kA

      25, 31.5,40

      7

      Rated peak withstand current

      kA

      63, 80,100

      8

      Rated breaking duration

      s

      4

      9

      Rated short-circuit breaking
      current

      kA

      25, 31.5,40

      10

      Rated short circuit making
      current(peak)

      kA

      63, 80,100

      11

      Rated breaking order

      0-0.3s-CO-180s-CO

      12

      Breaking time

      ms

      ≤80

      13

      Rated short-circuit cirrent
      breaking times

      times

      20

      14

      Rated single capacitor device
      ON-OFF current

      A

      630

      15

      Rated single back-to-back
      capacitor device current

      A

      400

      16

      Rated operating voltage

      V

      AC110/220, DC110/220

      17

      Mechanical life

      times

      10000

      18

      Contactor opening distance

      mm

      22±2

      19

      Contactor contact trip

      mm

      7.5±1.5

      20

      Average speed for closing

      m/s

      0.65±0.15

      21

      Average speed for opening

      m/s

      1.8±0.2

      22

      Closing time

      ms

      45 - 100

      23

      Opening time

      ms

      40-100

      24

      Contact closing bounce time

      ms

      ≤3

      25

      At the different period of three
      consistency

      ms

      ≤2

      26

      Buffered travel

      mm

      13±1

      27

      Leading electrical circuit
      resistance(excluding contactor arm)

      μΩ

      ≤40

      28

      the thickness of the contact wear

      mm

      3

      Installation

      Installation and test run:

      • 5.1Checking before installation

        Check the specification of the breaker complies with the contract, and if the documents and the accessories provided with breaker are complete, if there is any injury on the surface of the breaker and if the isolated drum is damaged, also check the vacuity of the vacuum are-chute with industrial frequency voltage withstand method, switch tripping and apply industrial frequency voltage 95kv for 1 min at the fracture and there should be no flash-over or breaking.

      • 5.2Test

        Check the circuit breaker box in good condition generally does not require re-commissioning, only when that circuit breakers do not meet the technical requirements or replacement of critical components, the need to debug the circuit breaker to conform to the technical requirements.
        First, adjust the vacuum interrupter moving conductive rod and rod ends under the oil buffer height, so that the vacuum interrupter contact opening distance of 20±2 mm, insulated rod with adjustable length, so that the contact travel of 7.5±1.5 mm; then check the connecting shaft and oil buffers are normal, finally, regulatory agencies to make normal operation, requiring either manual, electric control, energy storage, switching, and other sub-actions should not be a gate wiring.